Dead Load, Imposed Load and Wind Load on Solar Structures: IS 875 Parts 1, 2 and 3 Explained

by Solyug Energy28 November 20260 Comments
What loads act on a solar mounting structure, how IS 875 Parts 1, 2 and 3 treat them, how each is converted into model loads, and what goes wrong when assumptions are poor.

Dead Load, Imposed Load and Wind Load on Solar Structures

A solar mounting structure is designed for a set of loads, each with its own source, direction and uncertainty. If one of them is missed or mis-sized, the rest of the design, however careful, is built on a wrong base. This article explains each major load, the part of IS 875 that governs it, and how it is turned into input for the analysis model. It is a companion to our pillar guide on solar structure design using STAAD.Pro.

How IS 875 covers solar loads

Load

Source

Notes

Dead load

IS 875 (Part 1): unit weights of building and stored materials

Plus manufacturer data for modules and accessories

Imposed (live) load

IS 875 (Part 2)

For solar tables, maintenance or access loading needs a stated, justified basis

Wind load

IS 875 (Part 3):2015 and amendments

See wind load calculation as per IS 875 Part 3

Snow load

IS 875 (Part 4)

Only for sites with snowfall

Special loads and combinations

IS 875 (Part 5)

Combination rules and special actions

Seismic load

IS 1893 (Part 1)

Where applicable

 

IS 875 was written for buildings and structures in general. It does not contain solar-specific load models, so engineers apply the closest provisions and document the reasoning.

Dead loads

Dead loads are permanent. For a solar table they include:

•       Solar modules. Use the weight on the manufacturer's datasheet, per module and per square metre of module surface.

•       Mounting accessories: rails, clamps, bolts and brackets.

•       Purlins, rafters, columns and bracing. The analysis program can generate self-weight from the section properties. IS 875 (Part 1) gives unit weights of materials such as steel and concrete if hand checks are needed.

•       Permanent equipment: cable trays, string boxes, inverters mounted on the structure, walkways and handrails.

On rooftops, the added dead load is also applied to the existing building, which is why roof assessment matters (see rooftop solar structure analysis using STAAD.Pro).

Imposed and maintenance loads

IS 875 (Part 2) gives imposed loads for floors and roofs. A solar table is neither, so the designer must decide which provisions are appropriate and state the assumption. Common practice is to consider a maintenance load for cleaning and inspection, for example a concentrated load at a purlin or a distributed allowance, but the value and arrangement should be taken from the project specification, the module manufacturer's guidance and a reasoned reading of the code, rather than copied from another project. Where people will walk on walkways or platforms attached to the structure, those elements are designed as access structures with appropriate imposed loads.

Wind loads

Wind produces pressure, suction (uplift) and horizontal force. It is usually the governing load. The key steps are in the wind load calculation article. For load definition, remember that:

•       Wind pressure and suction act normal to the module plane.

•       Wind can act from several directions, and each direction can produce a different governing case for different members.

•       The horizontal component sets sliding and overturning demand for the foundation.

Seismic loads

Where the project location and the authority require it, seismic loads are calculated under IS 1893. Lightweight steel tables often have small seismic demand compared with wind, but that conclusion must be shown by calculation for the site and structure, and heavier elements such as ballast or rooftop equipment can change it. Note that IS 1893 has recently changed: a 2025 revision was published and then reported to be rolled back in March 2026 with the 2016 edition restored. Confirm the edition in force with BIS and your client before calculating.

Construction and temporary loads

Installation sequence can load a partially built structure differently from the finished one, for example before bracing is complete or when modules are stacked temporarily on a roof. Where the contractor's method creates such conditions, they should be checked or controlled by method statement.

Converting loads for the analytical model

Loads are turned into model input in three steps.

1.       Convert surface loads to line loads. Multiply the area load by the tributary width of each purlin to get kN/m along the purlin.

2.       Resolve into directions. Gravity loads act vertically, wind acts normal to the module plane. For a tilt θ, a vertical load w on the inclined surface has a component w cos θ normal to the surface and w sin θ along the slope.

3.       Apply with correct signs and cases. Use separate primary load cases for dead, maintenance, each wind direction and seismic, and combine them later.

Worked illustration with assumed values

Continuing the assumed table from our wind article: 24 modules, each 2.2 m × 1.1 m (area 2.42 m²) and assumed 27 kg each; tilt 15°; table sloping length 4.4 m, width 13.2 m.

Item

Calculation

Result

Module weight per m²

27 × 9.81 / 2.42 / 1000

0.11 kN/m²

Allowance for rails and clamps (assumed)

 

0.05 kN/m²

Dead load on inclined surface (excluding steel)

0.11 + 0.05

0.16 kN/m²

Tributary width per purlin (4 purlins across 4.4 m, assumed)

4.4 / 4

1.1 m

Dead line load per purlin

0.16 × 1.1

0.176 kN/m (vertical)

Component normal to the surface

0.176 × cos 15°

0.170 kN/m

Wind uplift line load (pressure 1.045 kN/m², assumed)

1.045 × 1.1

1.15 kN/m

Wind downward line load (pressure 0.836 kN/m², assumed)

0.836 × 1.1

0.92 kN/m

 

The self-weight of the steel is added by the analysis program. These are illustrative values, not recommendations for any real project.

How incorrect load assumptions affect the design

•       Missed uplift case: columns and foundations are sized only for compression, and fail in tension.

•       Wind pressure too low: purlins and connections are under-designed. Deflection or buckling appears first under strong wind.

•       Module weight taken from the wrong datasheet: small effect on steel, but a large one on rooftop capacity checks and ballast.

•       Dead load overestimated in uplift: dead load that resists uplift must be reduced by the code's partial factor in the stability case, otherwise the uplift capacity is overstated.

•       Maintenance load ignored: local damage to purlins or modules when people work on the array.

•       Seismic ignored where required: a compliance gap and possible rejection by the reviewing authority.

Common mistakes

•       Using self-weight in the model and also adding the steel weight manually

•       Adding module weight along the vertical when the model expects load along local member axes

•       Using the same load case for pressure and suction

•       Applying maintenance load as a permanent load in all combinations

Frequently asked questions

What loads act on a solar mounting structure?

Dead load, imposed or maintenance load, wind load (pressure, suction and horizontal force), seismic load where applicable, snow in cold regions and temporary construction loads.

Which parts of IS 875 apply to solar structures?

Part 1 (dead), Part 2 (imposed), Part 3 (wind), Part 4 (snow, where relevant) and Part 5 (special loads and combinations). None includes solar-specific models, so judgement is needed.

Is seismic load considered for solar structures?

Where the location and authority require it. Light tables may be governed by wind, but the check should be made, and the applicable IS 1893 edition confirmed.

How do I convert module weight into a load on purlins?

Divide the module weight by its area, add accessories, multiply by the purlin's tributary width and resolve into components normal and parallel to the member.

Is maintenance load required on a solar structure?

Most design bases include one, but its value and form should be justified from the project requirements, the module manufacturer's guidance and the relevant code provisions.

Why does dead load matter if wind governs?

Dead load resists uplift and contributes to combinations that govern columns and foundations, so it must be right, and used with the correct partial factor.

Conclusion

Each load has a source, a direction and a code basis. Writing those down in the design basis, and converting them carefully to model input, prevents most of the errors that appear later in analysis.

Get your load assumptions reviewed

Solyug Energy's solar structural consultancy covers load definition, STAAD.Pro analysis and engineering reports. For wind-critical sites, see our STAAD Pro wind analysis service, or contact us with your project details.

#dead load#imposed load#wind load#IS 875#solar structure loads#load calculation#seismic load#solar mounting structure

Comments (0)

No comments yet. Be the first to share your thoughts!

Leave a Comment

Chat with us
SOLYUG ENERGY
SOLYUGENERGY

SOLAR DESIGN & CONSULTANCY

Let's Engineer Your Next Solar Project.

Looking for reliable solar engineering and design solutions? Partner with Solyug Energy for precise solar layouts, detailed engineering, structural consultancy and performance-driven project designs. With 520MW+ project experience across India, Africa and the Gulf, our team is ready to support your next solar project.
520MW+
PROJECT EXPERIENCE
5+
YEARS EXPERIENCE

Explore Our Solar Engineering Expertise

Serving EPCs, developers & businesses across India, Africa & the Gulf.