Load Cases and Load Combinations for Solar Mounting Structures: Strength, Serviceability and Uplift
Load Cases and Load Combinations for Solar Mounting Structures
A solar structure is never checked against a single load. It is checked against the worst plausible combination of loads, with each load multiplied by a factor reflecting its uncertainty and how it acts with the others. Getting the combinations right is what turns a set of individual loads into a safe design. This article is part of our series on solar structure design using STAAD.Pro.
Code verification required: Load factors and combination rules depend on the design code and its edition. IS 800:2007 uses a limit-state format, and IS 800:2026 has now been published, with IS 800:2007 reported to be scheduled for withdrawal on 28 April 2027. The factors shown below follow the commonly cited limit-state format and are for explanation. Before using any factor, read the combination table in the edition your project adopts, and the IS 875 (Part 5) provisions on combinations. We have not verified clause numbers or factor values in the 2026 edition.
What a load case and a load combination are
• A load case (primary load case) is a single type of loading applied alone: dead load, maintenance load, wind from one direction, an earthquake direction.
• A load combination is a defined mixture of load cases with factors, for example 1.5 times the dead load case plus 1.5 times a wind case.
Combinations exist because loads act together and the structure's response must be checked for the unfavourable arrangement. Code factors account for the variability of each load and for the low probability that all loads reach their peak at once.
Why combinations are needed
• Different members have different governing cases. A purlin may be governed by uplift while a column is governed by downward load.
• Dead load can help or hurt. It adds to downward cases but stabilises against uplift, so it is factored differently in the two situations.
• Wind direction changes everything. Forces in bracing and columns can reverse when the wind direction changes.
• Serviceability needs a different basis from strength. Deflection is checked at unfactored or lightly factored loads.
Load cases for a solar structure
Primary case | Description |
DL | Self-weight of steel, modules, rails, clamps and permanent equipment |
IL / MAINT | Maintenance or access load, defined in the design basis |
WL1 to WLn | Wind in each direction, with separate downward and uplift cases |
EL | Earthquake load, where applicable |
SL | Snow, where relevant to the site |
TEMP | Thermal effects, where long runs are restrained |
How combinations are built
Strength combinations (limit state of strength) apply partial safety factors to each action. For the commonly used limit-state format, representative combinations for a solar table look like the following. All factors are illustrative of the usual format and must be confirmed against your governing code.
Combination | Typical form | Purpose |
Gravity | 1.5 DL + 1.5 IL | Maintenance and dead load, no wind |
Wind, downward | 1.5 DL + 1.5 WL (downward case, each direction) | Peak compression and bending in columns, rafters, purlins |
Wind, uplift | 0.9 DL + 1.5 WL (uplift case, each direction) | Peak tension, anchor and foundation uplift, member reversal |
Wind with imposed | 1.2 DL + 1.2 IL + 1.2 WL | Only if the design basis requires imposed load to act with wind |
Seismic | 1.5 (DL + EL) and 0.9 DL + 1.5 EL | Where the site and authority require |
Serviceability | 1.0 DL + 1.0 WL (each direction); 1.0 DL + 1.0 IL | Deflection checks |
The 0.9 factor on dead load applies where dead load acts to resist overturning, uplift or stress reversal, as in the uplift case. The 1.5 factor applies where dead load adds to the effect being checked. Using 1.5 on dead load in an uplift case overstates the resistance and is unsafe.
Different wind directions
Each wind direction has a downward and an uplift variation, so the combination count multiplies quickly. For example, front wind, rear wind, wind along the table and two oblique directions, each with both signs, give around ten wind-based combinations. Do not discard any without understanding why it cannot govern. In the model, give each case a descriptive title so the governing case can be recognised in the output.
Governing load cases
For each member group, find the combination that gives the highest utilisation. The governing case often differs among:
• Purlins: frequently uplift (flange in compression, lateral-torsional buckling) or downward bending
• Rafters: the case with the highest bending and axial combination
• Columns: downward case for compression and buckling, uplift case for tension and connections
• Bracing: the direction that gives the highest tension or compression
• Foundations: maximum uplift and maximum compression, which usually come from different combinations
Load reversal and uplift
Wind can reverse forces in members that appear to carry compression under gravity. Slender bracing and columns that are fine in compression may need checking in tension and vice versa, and connections must resist the reversed force. Check for reversal explicitly by comparing the sign of axial force and moment across all combinations rather than looking at one governing case.
Defining combinations in STAAD.Pro
Bentley's documentation describes combinations as a LOAD COMBINATION command with a number and title, followed by pairs of primary case number and factor, for example case 1 with a factor of 1.5 and case 2 with a factor of 1.5. Two important points from the documentation:
• Combinations of primary cases are algebraic combinations of analysis results, so they are not appropriate for nonlinear analysis, and the load combination command should not be used to obtain secondary effects of combined cases in P-delta, tension/compression-only or nonlinear analyses.
• STAAD.Pro also has an automatic load combination generator that builds combinations from code-defined rules and the load types you select. Check whether your version and code selection include the rules you need, and check the generated set rather than assuming it is complete.
A short example in the documented form:
LOAD COMBINATION 101 1.5 DL + 1.5 WL FRONT DOWN 1 1.5 2 1.5 LOAD COMBINATION 102 0.9 DL + 1.5 WL FRONT UPLIFT 1 0.9 3 1.5 |
Case numbers here are placeholders. Confirm syntax against your installed version's help.
Worked illustration with assumed values
Using the assumed purlin line loads from our earlier articles (dead 0.170 kN/m normal, wind downward 0.920 kN/m, wind uplift 1.150 kN/m) and the factors above:
Combination | Calculation | Resulting normal line load |
1.5 DL + 1.5 WL (down) | 1.5 × 0.170 + 1.5 × 0.920 | 1.635 kN/m toward the surface |
0.9 DL + 1.5 WL (up) | −0.9 × 0.170 + 1.5 × 1.150 | 1.572 kN/m away from the surface |
Serviceability, downward | 0.170 + 0.920 | 1.090 kN/m |
Serviceability, uplift | −0.170 + 1.150 | 0.980 kN/m |
The two strength cases are close, so both would need to be checked for the purlin, but the support conditions and lateral restraint differ between them, so the utilisation will not be the same. This is why both are retained.
Common mistakes
• Applying 1.5 to dead load in uplift cases
• Combining imposed load with wind without a basis
• Defining combinations for one wind direction only
• Using combination results for P-delta or nonlinear checks where this is invalid
• Using factors from a different code (for example another country's) with Indian load definitions
• Not re-checking combinations after a code edition changes
Frequently asked questions
What is a load combination?
A defined set of load cases combined with factors to represent a realistic worst case for strength or serviceability.
Why are load combinations needed?
Because structures see several loads at once, because dead load helps in some cases and hurts in others, and because different members govern under different combinations.
How is uplift combined with dead load?
Normally with a reduced dead load factor where dead load resists uplift, and a full wind factor, using the factors in the governing code.
Which combinations does a solar structure need?
Gravity, wind downward, wind uplift for each direction, seismic where applicable and serviceability combinations. Imposed load with wind only if the design basis requires it.
Can STAAD.Pro generate load combinations automatically?
It has an automatic generator driven by code-defined rules. Check that the rules match your governing code and edition, and review the output.
Do load factors change with IS 800:2026?
Possibly. We have not verified the 2026 edition's tables, so confirm against the official copy.
Conclusion
Combinations convert loads into design checks. A short, well-documented list that includes uplift, each wind direction and serviceability is far more valuable than a long list generated without understanding.